季晓春1,王建华2,嵇保健3 曹武2,刘建春1
(1. 安科瑞电气股份有限公司,上海市,201801
2. 江苏省智能电网技术与装备重点实验室,东南大学电气工程学院,江苏省 南京市 210096
3. 南京工业大学自动化与电气工程学院,江苏省 南京市210009)
Three Phase Shunt APF-STATCOM Harmonic, Unbalance Load and Reactive Current Compound Control Strategy in smart Distributed GridJI Xiaochun1, WANG Jianhua2,JI Baojian3, Cai Wu2, JIANG Long1, Zhou Zhong
Abstract: Based on compound power quality concept, this paper proposed a compound harmonic, negative and reactive current compensation strategy for harmonic current, load imbalance and low power factor issues in smart distributed grid. Key factors are presented in detail. Corresponding three phase four line APF-STATCOM simulation and experimental tests and field operation results verify the compound control and compensation concept.
Key words: Smart distributed grid;active power filter(APF); static synchronous compensator(STATCOM);harmonic;unbalanced load;reactive;compound control
摘要:基于电能质量复合控制思想,针对智能配电网中谐波电流、负载不平衡、功率因数较低问题,给出一种谐波、负序及无功电流复合补偿策略,并给出关键参数设计方法。相关APF-STATCOM仿真、实验验证及产品现场运行实测结果验证了复合控制思想及补偿策略正确性及可行性。
关键词:智能配电网;有源电力滤波器;静止同步补偿器;不平衡负载
近年来,出于节能环保的考虑,配电网终端供电系统中电力电子变换装置应用越来越广泛,如照明、办公、空调、电梯等相关供电系统,但这类非线性电能变换装置在改善用户端电能质量同时,往往诱发配电网侧谐波及无功电流问题,线损、中线及变压器过热、电表计量不准,甚至保护误动作等现象时有发生。传统无源滤波及投切电容器补偿尽管能够解决上述问题,且成本较低,但无法实时连续调节,存在过补偿、无功倒送甚至诱发配电网谐振可能性[1-3]。
为**智能配电网终端用户高品质定制电力供应,随着瞬时功率理论及电力电子器件的发展,取代无源滤波及电容器无功补偿装置,其主电路拓扑结构及设计、谐波电流检测、补偿方法、控制及调制策略,以及启动特性均是业界研究及工业应用的持续热点话题[2-6]。
由于如今智能配电网中电能质量问题已经不再是一个单一的问题,而是一个非常复杂的系统问题。如图1所示,某公用设施配电系统中同时存在谐波电流、负载不平衡及功率因数较低等问题。电能质量复合控制技术逐渐被学术界及工业界提上研究日程[7-8]。
图1 实际配电网电能质量问题
Fig. 1 Power quality issue in a real distributed grid
本文研究了智能配电网环境下,同时面对时变谐波电流、不平衡负载及无功问题,给出一种谐波、负序和无功电流复合补偿策略,及其关键参数设计方法。相关仿真、实验验证及产品现场运行实测结果验证了该控制策略的正确性及可行性。
APF-STATCOM电路结构及工作机理
图2 并联APF-STATCOM框图
Fig. 2 An APF-STATCOM diagram
如图2所示,该并联APF-STATCOM采用两电平三相四桥臂电压源逆变器拓扑,其中**桥臂实现谐波及无功补偿,四桥臂立用于控制中线电流。这是由于三相四线制系统中,当负载不平衡时,中线往往流过较大零序电流,其不同于三相三线制系统。因此,增加与**桥臂解耦控制的四桥臂提供零序电流通路。此时APF-STATCOM产生一个与负载电流iL,abc中谐波、基波负序和零序分量之和相反的补偿电流iC,abc,使得电源电流iS,abc仅提供负载电流基波正序分量,确保源输出对称三相电流并提高功率因数。
其中中线电流分离检测、锁相环、谐波电流检测、直流电压控制、电流控制及PWM调制是实现高性能APF-STATCOM的关键。锁相环、直流电压控制等与三相三线制系统相同,在此不作详细介绍。
关键问题分析
1. 四桥臂中线电流分离检测及控制
考虑到不平衡的三相四线制电路中的负载电流iL,abc所包含的零序分量iN相等,均为
(1)
如图2所示,此时中线电流采样值iN,与中线零序电流分量补偿指令iNref一并作为四桥臂电流控制器输入,通过PI调节器得到调制信号获得四桥臂开关信号。
同时有,
(2)
(3)
(4)
式中,仅含正序分量及负序分量,便于后续采用三相三线系统中ip-iq谐波电流检测算法。
2. 谐波电流检测
图3 ?用d-q变换检测谐波的原理图
Fig. 3 The schematic diagram of the harmonics detecting method based on d-q rotating coordination transformation
传统基于p-q瞬时无功功率理论检测谐波电流方法受电压畸变及不对称影响较大,实际场合并不适用[9]。实际场合多采用加入锁相环PLL电路的ip-iq瞬时无功功率理论检测方法,具体如图3所示,相关变换为
(5)
(6)
提取不含零序分量的电流 ,通过Park变换,将基波分量在d-q-0 坐标中变换到0Hz处(或先经 变换再经dq变换亦可),用低通滤波器提取基波正序分量即可[5]。
图2中直流电压调节器输出值生成部分有功电流指令,用于稳定直流母线电压并补偿功率损耗部分。若为提高功率因数,可以同时补偿无功电流,此时基波负序无功电流指令值设定为0。后用负载电流减去基波电流正序分量,即可得到补偿负载电流中谐波分量和因负载不平衡导致的电流负序分量、零序分量的指令电流量以及无功电流正序分量的指令电流,实现APF-STATCOM功能。
3. 电流PR谐振控制器设计
由于APF-STATCOM跟踪的电流指令是多种频率正弦量的叠加信号,传统SPWM调制采用PI控制必定存在稳态误差和相位偏移,补偿效果不佳,往往采用电流滞环调制,但变频调制不可避免带来滤波器设计及噪声控制问题[9]。
通过旋转坐标变换可以将正弦信号变为直流信号,从而在新的坐标系下采用PI控制器。但在APF-STATCOM控制领域,必须在多个频率下进行坐标变换,计算复杂,不利于实际应用。近年来,针对正弦信号的提出的PR控制器,在可以避免旋转坐标变换,计算量大大降低的同时,获得与同步坐标系下的PI控制器相同控制效果:能无稳态误差地跟踪特定频率的正弦信号,重要的是可以对频率的谐波进行有选择地补偿。
(7)
(8)
式中 为谐振频率。
由式(7)可知,对直流系统而言,由于积分环节的存在,0 Hz处的增益高,从而系统可以实现无静差调节;对于交流系统,50Hz及其倍数次谐波,式(7)增益有限,式(8)由于谐振环节的引入,在相应频段有较高的增益。若跟踪的目标为基波 rad/s;若需补偿较高幅值的5次谐波,则有 rad/s。通常补偿谐波次数高至20或50次,尤其是幅值较高的奇次谐波。因此有,
(9)
图4所示为基波及三、五、七次谐波补偿用PR谐振控制器波特图,可以看出在相应频段电流控制器增益较高,有助于减小跟踪误差。
图4 ?PR谐振控制器波特图
Fig. 4 PR controller bode plots
仿真及实验验证
为验证所提出的谐波、负序及无功电流复合补偿策略,本文在Matlab Simulink环境下建立仿真平台。相关参数设置如下:输入三相四线制电压380V/50Hz,三相二管整流器非线性负载直流侧滤波电感1mH,电阻3.2Ω,三相二管整流器交流电抗0.4mH,APF-STATCOM并网电抗0.4mH,直流侧支撑电容4000μF,交流侧不平衡RL负载星型联接,电感值均为8mH,电阻值分别为5Ω,50Ω,500Ω,开关频率10kHz。
图5所示以A相为例,表明补偿后APF-STATCOM注入电流很好地抵消了负载电流的谐波电流,使得电网电流正弦化较好,实现了APF谐波补偿功能;同时电网电流与电网电压同频同相,功率因数接近于1,实现了STATCOM无功补偿功能。图6给出三相补偿结果,对称三相电流波形验证其具有较好抑制不平衡负载能力。
图5 A相补偿后电压电流波形(从上到下依次是电网电压/V、电网电流/A、补偿电流/A、负载电流/A,时间轴t/s)
Fig. 5 Phase A wave forms after compensation
图6 补偿后电网三相电压电流波形(从上到下依次是三相电网电压/V、三相电网电流/A,时间轴t/s)
Fig. 6 Three phase wave forms after compensation
图7进一步给出直流侧母线电压波形,可以看出APF-STATCOM在完成谐波补偿后,母线电压略有波动,但稳定在750V设定值附近。
图7 直流侧母线电压/V(时间轴t/s)
Fig. 7 Dc link bus voltage
图8及图9进一步给出工业样机内部测试结果,受实验条件限制,此时负载仅为整流性非线性负载,故负载电流及补偿电流与仿真有所区别,其主要体现了APF补偿功能。图10给出产品在现场投运结果,与图1相比,中性线电流由37A减小至5A,三相电流THD大不过3.4%,且对称性较好,充分验证了APF-STATCOM复合补偿功能。
图8 A相及B相补偿后网侧电流及负载电流(从上到下依次是A相电压、B相电流、A相负载电流、B相负载电流)
Fig. 9 Phase A &B grid & load current after compensation
图9 A相补偿后网侧电流、发出反向谐波电流及负载电流
Fig. 9 Phase A grid, inverse harmonic current & load current after compensation
图10 实际现场APF-STATCOM补偿后结果
Fig. 10 APF-STATCOM Compensation effects in practice
结论语
基于电能质量复合控制思想,针对智能配电网中谐波电流、负载不平衡、功率因数较低问题,提出一种谐波、负序及无功电流复合补偿策略。
仿真、工程样机试验及现场运行结果验证了基于该策略所实现的APF-STATCOM复合补偿功能。
文章来源:《电气应用》2014年 6期
参考文献
1.国家技术监督局.中国国家标准GB/T 14549-93电能质量公用电网谐波[S].北京:中国标准出版社,1994.
2.赤木泰文(Hirofumi Akagi)等(徐政 译).瞬时功率理论及其在电力调节中的应用[J].北京:机械工业出版社,2009.
3.王兆安,杨君,刘进军.谐波抑制和无功功率补偿。机械工业出版社,1998.
4.马莉,周景海,吕征宇,钱照明.一种基于dq 变换的改进型谐波检测方案的研究[J].中国电机工程学报,2000,20(10):55-63.
Ma Li,Zhou Jinghai,LüZhengyu,Qian Zhaoming. An improved harmonic detecting approach based on dq rotating coordination transformation[J].Proceedings of the CSEE,2000,20(10):55-63(in Chinese).
Zeliang Shu, Yuhua Guo, and Jisan Lian. Steady-state and dynamic study of active power filter with efficient FPGA-based control algorithm [J].IEEE Transactions on Industrial Electronics,2008,55(4):1527- 1536.
5.赵国鹏,林少伯,韩民晓.基于补偿特性的并联型有源电力滤波器直流侧电压取值分析[J].电力系统自动化,2012,36(14):83-87.
Zhao Guopeng,Lin Shaobo,Han Minxiao.Design of voltage in DC link of parallel-type active power filter based on compensation characteristics[J].Automation of Electric Power Systems,2012,36(14):83-87 (in Chinese)
6.单任仲.并联型复合电能质量扰动及补偿的控制方法与实现 [D].博士学位论文,北京:华北电力大学,2010.
7.刘海波,毛承雄,陆继明,王丹.四桥臂三相四线制并联型APF—STATCOM [J].电力系统保护与控制,2010,38(16):11-17.
Liu Haibo,Mao Chengxiong, Lu Jiming,Wang Dan.Three-phase four-wire shunt APF-STATCOM using a four-leg converter [J].Power System Protection and Control,2010,38(16):11-17 (in Chinese).
8.曹武.谐波立补偿有源滤器关键技术研究[D].硕士学位论文,南京:东南大学,2011.
技术咨询:
杨馨,女,本科,安科瑞电气股份有限公司,主要研究方向为智能电网供配电,Email: 安科瑞@手机:
QQ:安科瑞
词条
词条说明
安科瑞Acrelcloud-6000安全用电管理平台在新疆阿克苏地区库车县的应用
杨馨 安科瑞电气股份有限公司,上海 嘉定 201801; 摘要 安科瑞Acrelcloud-6000安全用电管理平台是针对我国当前电气火灾事故频发而创新的一套电气火灾预警和预防管理系统,该系统是基于移动互联网、云计算技术、通过物联网传感终端(现场监控模块、传输模块),将供电侧、用电侧电气安全参数实时传输至云服务器。安全用电管理云平台可以不受时间、地点、环境的限制,自行选择合适的方式(本
关键词:医院电气火灾;起因;预防0引言由于医院人流量大,各种大型检查设备相对比较集中,压力容器、化学试剂、被褥纸张等易燃易爆物品多,因此火灾隐患多,且造成的火灾范围广,影响深,损失惨。例如,锅炉房、供应室消毒锅、高压氧舱液氧罐等压力容器的操作是否达到标准化、规范化,安全阀是否按要求定期检验;洗衣房、被服中心、病区小仓库、放射科储片室、病案室、图书室的易燃物品,手术室、病理科、检验科、制剂室、**室
杨馨安科瑞电气股份有限公司,上海 嘉定 201801;摘要:介绍杭州创富春天电商产业园远程预付费电能管理系统,采用智能预付费仪表进行远程分合控制,达到预付费使用功能。系统采用现场就地组网的方式,组网后通过现场总线通讯并远传至后台,通过Acrel-3200型远程预付费电能管理系统实现配电回路用电的收费和能效管理。关键词:商业办公楼;预付费电能表;Acrel-3200型;远程预付费电能管理系统&nbs
杨馨安科瑞电气股份有限公司 上海 嘉定【摘要】:针对大型公共建筑能耗高且能源管理不合理的问题,利用计算机网络技术、通讯技术、计量控制技术等信息化技术,实现能源资源分类分项计量和能源资源运行监管功能,清晰描述建筑内总的用能现状;实时监测各供电回路的电压、电流和功率等电力参数,识别有效负荷与无效能耗,从而可通过技术或行为节能方式,实现建筑的有效节能。1 项目概述 路林市场市场占地约300亩
公司名: 安科瑞电气股份有限公司
联系人: 杨馨
电 话: 021-69156372
手 机: 18702111791
微 信: 18702111791
地 址: 上海嘉定嘉定上海市嘉定区育绿路253号
邮 编:
供应ISPS应急电源ISPS节能电源照明动力ISPS电源ISP0KVA
¥12000.00
¥77.66
¥3500.00
¥800.00