Configuration procedure

    Configuration procedure

    Proceed as follows to create a new project in the TIA Portal and add a SIMATIC Drive Controller:

    Creating a project

      Start TIA Portal.

      Select the action "Start" > "Create new project" in the portal view.

      Assign a name for the new project under "Project name".

      Set the storage location with the "..." button.

      If required, enter comments in the Comment field.

      Click the "Create" button to create the project.

    You have created the project and are currently in the portal view. To continue with the configuration, switch to the project view.

    Adding a SIMATIC Drive Controller to the project

      Select "Add new device" in the project tree.

      In the "Add new device" dialog, select the device version you are using under "Controller" > "SIMATIC Drive Controller" and the firmware version of the device under "Version".

      You use the "Open device view" checkbox to specify whether the hardware configuration view is to be opened once the device has been created. Keep the checkbox selected if you want to configure the CPU next.

      Click OK to confirm the new device.

    You have added the SIMATIC Drive Controller to the project and can now continue with configuration, parameter assignment and programming.

    Display of the SIMATIC Drive Controller

    When you add a SIMATIC Drive Controller to the project, by default:

    A "Drive Controller_a" group is generated

    Two devices are added to the group, for example:

    - PLC_b [CPU 1504D TF] and

    - Integrated_c [S120, CPU 150xD]


    图片: SIMATIC Drive Controller in the project tree, device collapsed

    SINAMICS Integrated is only created if Startdrive is installed. Both devices have already been joined in a network over the PROFIdrive Integrated_d subnet.

    The respective instance numbers (a, b, c, d) are assigned by STEP 7 depending on the objects already present in the project.


    图片: SIMATIC Drive Controller network view

    CPU (e.g. PLC_1) and integrated drive control (e.g. Integrated_1) are modeled as separate devices. You can also move the devices as required to other groups and delete the "Drive Controller" group. You can also add other devices to the "Drive Controller" group, for example a CU320-2 PN, if you require more than six servo drives.


    提示

    Adding SIMATIC Drive Controller directly to group

    You can add the SIMATIC Drive Controller directly to a group folder in the project tree even if the group folder is a subfolder:

      Select the required group.

      Go to the menu bar or shortcut menu and select "Add" > "Device".



    Creation options

    The CPU and SINAMICS Integrated are by default created in a shared group folder in the project tree.

    To change this behavior, activate or deactivate the relevant options for the SIMATIC Drive Controller under "Settings" -> "Hardware configuration" -> "Device-specific settings".


    图片: Creation options for creating a SIMATIC Drive Controller

    The table below sets out the benefits of configuration with or without grouping.

    列表: Guide to groupingProjectGrouping

    With "Drive Controller" grouping

    Without grouping or user-specific grouping

    Actions apply to all devices in a group, for example

    - Go online

    - Load to/from device

    - Copy

    You can add additional devices to the group as required, for example

    - with CU320-2

    - with I/O system

    Greater flexibility in project structure in the project tree, for example

    - by machine/plant modules

    - by CPUs and drives, in separate groups

    If you want to create the SIMATIC Drive Controller without the integrated drive, deselect the "Including SINAMICS Integrated" option.

    Deselecting this option can, for example, be useful in the following cases:

    You are copying a previously configured SINAMICS Integrated drive control from another project.

    The project is to be processed by another user without SINAMICS Startdrive.

    SINAMICS Integrated is not to be configured until later.

    SINAMICS Integrated is not being used, for example, because another drive system is being used.

    "Drive Controller" group

    For the "Drive Controller" group, you have a range of functions to choose from in the menu bar, toolbar and shortcut menu. With "Go online", for example, you can go online with all devices in the group.

    The functionality supported by a given device depends on the device and state. For example, the function "Download to device" is supported by the SINAMICS Integrated but not by the CPU when there is an active online connection. The "Load preview" dialog provides relevant information and suggestions for actions for loading.


    图片: Load preview


    Subsequently configuring SINAMICS Integrated

    Requirements: STEP 7 Professional and SINAMICS Startdrive are installed.

    Proceed as follows if your project only contains the CPU of a SIMATIC Drive Controller and you want to configure the missing SINAMICS Integrated.

      Select "Add new device" in the project tree.

      In the "Add new device" dialog, go to "Drives" > "Drives & starters" > "SINAMICS drives" > "SINAMICS S120 Integrated for SIMATIC" and select SINAMICS Integrated, and select the firmware version of the device under "Version".

      Click OK to confirm.

    Result: SINAMICS Integrated has been added to the project tree and can be networked with the CPU.

    Subsequently configuring a CPU

    Requirements: STEP 7 Professional and SINAMICS Startdrive are installed.

    Proceed as follows if your project only contains a SINAMICS Integrated of a SIMATIC Drive Controller and you want to configure the missing CPU.

      To ensure that only the CPU (without SINAMICS Integrated) is created, deselect the "Including SINAMICS Integrated" option under "Settings" > "Hardware configuration" > "Device-specific settings". Also deselect the "With Drive Controller group folder" option if you do not want a group folder to be created. Alternatively, you will need to delete the components you do not require.

      Select "Add new device" in the project tree.

      In the "Add new device" dialog, select the relevant device version under "Controller" > "SIMATIC Drive Controller" and the firmware version of the device under "Version".

      Click OK to confirm.

    Result: The CPU has been added to the project tree and can be connected to the SINAMICS Integrated .

    Replacing devices in STEP 7

    The following section explains how to replace a SIMATIC S7-1500 CPU with a SIMATIC Drive Controller in an existing project or vice versa.

      Select the device to be replaced in the project tree and right-click to open the shortcut menu.

      Select the "Replace device..." option

      Select the module you want to use in the right-hand column. The "Compatibility information" section indicates whether the devices to be replaced are compatible and whether or not and, if so, which configurations will be lost in the process.

      Click "OK" to confirm.

    When replacing devices, remember that the SIMATIC Drive Controller consists of two networked devices – a CPU and a SINAMICS Integrated.

    Replacing a modular SIMATIC S7-1500 CPU with a SIMATIC Drive Controller (CPU)

    If you replace a modular SIMATIC S7-1500 CPU with a SIMATIC Drive Controller, the configurations at the integrated PROFINET interfaces and at the integrated PROFIBUS interface are retained. In other words, the interfaces are mapped to an interface of the same type.

    Configurations of the onboard I/O of S7-1500 compact CPUs are not applied. Please also note the compatibility information in the device replacement dialog.

    The centralized I/O in the S7-1500 automation system is moved to the "unplugged modules" area. If required, copy the I/O to a distributed I/O ET 200MP system before device replacement.

    A connected SINAMICS S120 CU320-2 remains connected – it is not swapped out for a SINAMICS Integrated. If you require a SINAMICS Integrated, you need to create it manually.

    Replacing a SIMATIC Drive Controller (CPU) with a modular SIMATIC S7-1500 CPU

    For the device replacement, PROFIdrive Integrated is removed and SINAMICS Integrated remains as a non-networked device in the project. You can connect SINAMICS Integrated to a SIMATIC Drive Controller CPU again at a later time.

    If you no longer need SINAMICS Integrated, manually delete it from the configuration.

    Configurations at interface X142 are not applied.


    提示

    Device replacement with other CPU classes (for example ET 200SP CPUs or ET 200pro CPUs) is not possible.



    Replacing SINAMICS Integrated with SINAMICS S120 CU320-2 and vice versa

    Device replacement is currently not supported


    上海腾希电气技术有限公司专注于西门子PLC,V90伺服,V20变频器等, 欢迎致电 13681875601

  • 词条

    词条说明

  • 编辑对象

    编辑对象选择对象下表列出了如何选择单个对象(例如,项目树中的设备):功能键盘快捷键菜单命令选择位于左侧、右侧、上方或下方的对象 跳转到当前界面区内的**个对象选中当前激活的界面区中的**个对象。例如,在项目树中位于**部的项目节点。 跳转到当前界面区内的最后一个对象选中当前激活的界面区中的最后一个对象,例如,项目树中的最后一项。<

  • 连接表的筛选

    连接表的筛选筛选图片: 连接表(此处:IEC)表标题下方**行可在 DNP3 和 IEC 连接表中用作筛选条件。可以使用筛选功能来限制对可组态用户和连接选项的选择。使用筛选功能可减少可能的组合数并提高透明性。如果已创建某些连接分段,可在筛选单元格中键入重复的字符串(部分名称)来启用筛选功能。筛选单元格将以彩色**显示。现在,只有相应列中包含此字符串的连接分段才会显示在表中。筛选功能适用于以下各列:

  • BasicTask_* FC

    BasicTask_* FC块版本块可用于不同 CPU 类型的以下版本:BasicTask_B用于 S7‑1500 CPU用于 S7‑1500 CPU 的块不能用于 S7‑400 CPU。BasicTask_B用于 S7‑400 CPU用于 S7‑400 CPU 的块不能用于 S7‑1500 CPU。BasicTask_X用于使用合用线的 S7‑300 CPUBasicTask_P用于不使用合用线

  • SMART通过软件固件更新

    CPU 通过 RS485 接口从软件操作进行固件更新S7-200 SMART 编程软件,从 V2.3 开始具有固件更新的功能。S7-200 SMART V2.3 CPU 系列包含十二种 CPU 型号,分为两条产品线:紧凑型产品线和标准型产品线。紧凑型 CPU 四种: CPU CR20s、CPU CR30s、CPU CR40s 和 CPU CR60s ,V2.3 版本不适用于 CR40 和 CR 6

联系方式 联系我时,请告知来自八方资源网!

公司名: 上海腾希电气技术有限公司

联系人: 田礼科

电 话: 021-37660026

手 机: 13681875601

微 信: 13681875601

地 址: 上海松江上海市松江区广富林路4855弄星月大业**88号4楼

邮 编:

网 址: shtxjd.cn.b2b168.com

八方资源网提醒您:
1、本信息由八方资源网用户发布,八方资源网不介入任何交易过程,请自行甄别其真实性及合法性;
2、跟进信息之前,请仔细核验对方资质,所有预付定金或付款至个人账户的行为,均存在诈骗风险,请提高警惕!
    联系方式

公司名: 上海腾希电气技术有限公司

联系人: 田礼科

手 机: 13681875601

电 话: 021-37660026

地 址: 上海松江上海市松江区广富林路4855弄星月大业**88号4楼

邮 编:

网 址: shtxjd.cn.b2b168.com

    相关企业
    商家产品系列
  • 产品推荐
  • 资讯推荐
关于八方 | 八方币 | 招商合作 | 网站地图 | 免费注册 | 一元广告 | 友情链接 | 联系我们 | 八方业务| 汇款方式 | 商务洽谈室 | 投诉举报
粤ICP备10089450号-8 - 经营许可证编号:粤B2-20130562 软件企业认定:深R-2013-2017 软件产品登记:深DGY-2013-3594
著作权登记:2013SR134025
Copyright © 2004 - 2025 b2b168.com All Rights Reserved